The datasheet says ±0.075 %. Installed on the separator, PT-102 is good to ±0.5 % of span, 6.8× worse, and nobody lied.

We give the V-100 pressure transmitter PT-102 its range, scale it to 4–20 mA, set the NAMUR NE 43 alarm currents and build its total probable error by root-sum-square.

Item Value
PT-102 range 0–20 barg on a 70 bar sensor (turndown 3.5:1)
12 barg normal 60 % of span = 13.60 mA
NAMUR NE 43 live 3.8–20.5 mA; fail ≤ 3.6 / ≥ 21 mA
Total probable error (RSS) ±0.102 bar = 0.51 % span = 0.85 % of reading
Largest term 5-year stability, 0.44 % span

Size it yourself: Design Hub Unit Converter. Tag letters explained in How to Read P&ID Part 3.